Hawke Ex Series Dimensions (mm)
Dimension Ex16 Ex25 Ex32 Ex40 Ex50 Ex63
A 114 145 149 155 151 145
B 91 123 127 132 129 123
ØC 33 41 46 59 66 83
ØD 37 49 57 65 76 90
E 116 148 152 158 154 148
ØF 32 45 51 59 70 83
G 15 15 40 40 15 15
H 28 28 36 57 43 43
J 51 51 59 65 66 66
ØK 26 36 42 52 64 77
Thread L M25 M32 M40 M50 M63 M75
M 54 54 61 67 59 59
N A/F 36 46 55 65 80 94
ØP 24 38 42 52 64 76
R 38 38 38 38 38 38
S 61 61 61 61 61 61
ØT 29 41 47 55 67 79
U 32 32 32 32 32 32
Thread V M16 M25 M32 M40 M50 M63
ØW 55 65 72 82 92 108
Click here for Ex Connector insert configurations
Click here for Connector nomenclature
Click here for Connector shell configurations

Number of circuits
you require (n)....................................

Define your current
requirement per circuit (I)...............amps

From your conductor size,define contact
resistance (R) from table 3 ..............ohms

**Input your values into the following equation to calculate the dissipated Wattage Dissipated Wattage =(Current (I)2 x Resistance (R)x number of circuits (n)

The maximum permittable
dissipated Wattage allowed is ...........watts

Define the upper ambient
temperature for your application ..........ºC
(See tables 1 &2)

Define the temperature
class (T)you require ...........................T
(See tables 1 &2)

From the relevant temperature
class (T)define your
Shell size ........................................Ex

Select an appropriate Insert from the
selection chart.
The information given is
based on 600v circuit.

Table 1 Table 2
Max. Ambient temperature of 40 °C
Connector Size Temperature Class
T6 T5
Ex 16 5W 7W
Ex 25 8W 11W
Ex 32 10.5W 14.5W
Ex 40 12W 17W
Ex 50 13W 20W
Ex 63 17W 29W
Max. Ambient temperature of 50 ºC
Connector Size Temperature Class
T6 T5
Ex 16 4W 6W
Ex 25 6W 10W
Ex 32 8W 12W
Ex 40 9W 14W
Ex 50 10W 17W
Ex 63 13W 24W
Table 3

flameproof connectors

Contact Size Contact Resistance Contact Rating **
1.5 mm 2 0.0073 ohms 10 amps
2.5 mm 2 0.0049 ohms 17 amps
6 mm 2 0.0059 ohms 30 amps
10 mm 2 0.004 ohms 78 amps
16 mm 2 0.004 ohms 78 amps
25 mm 2 0.0012 ohms 125 amps
35 mm 2 0.0012 ohms 125 amps


 
Hawke Asia Pacific pte
15 Little Road
#04-02
Singapore 536988
Tel +65 (282) 2242
Fax +65 (284) 4244
E-mail information@hawkeasia.com.sg
Hawke Cable Glands Ltd
Atlantic Works, Oxford Street West
Ashton-under-Lyne, Lancashire
OL7 0NA, U.K
Sales 0870 6060105
General + 44 (0)161 308 3611
Fax +44 (0) 161 308 5848
E-mail marketing@hawke-cable-glands.com
Hawke Cable Glands America L.C.
600 Kenrick, Suite C-10, Houston, TX.
77060, U.S.A.
Tel: +1 (281) 445 7400
Wats: (800) 354 9189
Fax +1 (281) 445 7404.
E-mail hawke@hawkeusa.com
www.ehawke.com

Click here to view our legal information page